Winding Failures

Good Stator Winding

Unfavorable operating conditions–electrical, mechanical or environmental–can dramatically shorten the life of a three-phase stator winding. The winding failures illustrated below typify what can happen in such circumstances. They are shown here to help you identify the causes of failure, so that, where possible, you may take preventive measures.

Compare the new stator winding (right) with the failed windings pictured below. 

(All photographs are copyrighted (c) 1985-2008 by EASA. All rights are reserved.)          


 

str01-f.jpg

Winding Single-Phased
(Wye-Connected)


A single-phased winding failure is the result of an open in one phase of the power supply to the motor. The open is usually caused by a blown fuse, an open contactor, a broken power line or bad connections.


 

str02-f.jpgWinding Single-Phased
(Delta-Connected)

A single-phased winding failure is the result of an open in one phase of the power supply to the motor. The open is usually caused by a blown fuse, an open contactor, a broken power line or bad connections.


 

str03-f.jpgWinding Shorted Phase-to-Phase

This type of insulation failure is typically caused by contaminants, abrasion, vibration or voltage surge.


 

str04-f.jpgWinding Shorted Turn-to-Turn

This type of insulation failure is typically caused by contaminants, abrasion, vibration or voltage surge.


 

str05-f.jpgWinding With Shorted Coil

This type of insulation failure is typically caused by contaminants, abrasion, vibration or voltage surge.


 

str06-f.jpgWinding Grounded at Edge of Slot

This type of insulation failure is typically caused by contaminants, abrasion, vibration or voltage surge


 

str06a-f.jpgWinding Grounded at Edge of Slot

This type of insulation failure is typically caused by contaminants, abrasion, vibration or voltage surge.


 

str07-f.jpgWinding Grounded in the Slot

This type of insulation failure is typically caused by contaminants, abrasion, vibration or voltage surge.


 

str08-f.jpgShorted Connection

This type of insulation failure is typically caused by contaminants, abrasion, vibration or voltage surge.


 

str09-f.jpgPhase Damage Due to Unbalanced Voltage

Thermal deterioration of insulation in one phase of the stator winding can result from unequal voltage between phases. Unequal voltages usually are caused by unbalanced loads on the power source, a poor connection at the motor terminal, or a high resistance contact (weak spring).

Note: A one-percent voltage unbalance may result in a six- to ten-percent current unbalance.


 

str10-f.jpgWinding Damaged Due to Overload

Thermal deterioration of the insulation in all phases of the stator winding typically is caused by load demands exceeding the rating of the motor.

Note: Under-voltage and over-voltage (exceeding NEMA standards) will result in the same type of insulation deterioration.


 

str11-f.jpgDamage Caused by Locked Rotor

Severe thermal deterioration of the insulation in all phases of the motor normally is caused by very high currents in the stator winding due to a locked rotor condition. It may also occur as a result of excessive starts or reversals.


 

str12-f.jpgWinding Damaged by Voltage Surge

Insulation failures like this usually are caused by voltage surges. Voltage surges are often the result of switching power circuits, lightning strikes, capacitor discharges and solid-state power devices.